Arc flash protection that is accurate right down to the label
Arc flash clothing, arc flash hoods, face shields and insulating gloves in class APC 1 and APC 2. For every product, the arc flash class, the cal rating (ELIM / ATPV) published by the manufacturer, and the manufacturer's documents.
View the range Advice for your team
Choose your arc flash class
The class is determined by the employer's arc flash risk assessment. In the box test (IEC 61482-1-2), the garment is exposed to a 400 V arc flash for 500 ms.
Tested at 4 kA
- Work jackets, trousers, overalls, shirts and sweaters
- Also available in high-vis and as rainwear
- Insulating gloves and face shields class 1
Tested at 7 kA
- Rain jackets and parkas
- Arc flash hood and face shields class 2
- Insulating gloves with APC 2
What is the cal rating?
The cal rating (arc rating) is the amount of heat energy from an arc flash in cal/cm² that the fabric withstands before a second-degree burn occurs. The higher, the more protection. There are three values, all from the open arc test (IEC 61482-1-1):
The complete outfit
Arc flash protection only works as a whole. Combine clothing with protection for the face, head and hands.

Jacket, trousers or overall
EN 61482-2 with APC 1 or APC 2, always as a closed suit.
Face shield
Class 1 or 2 (GS-ET-29 / EN IEC 62819), on the prescribed helmet.
Arc flash hood
Full protection of eyes, face and neck.
Insulating gloves
EN 60903 class 00 or 0, with arc flash class.APC class or cal rating?
Arc flash clothing has two types of values. They come from different tests and cannot be converted into each other.
APC 1 / APC 2
Also known as class 1 and 2 (old designation until 2014).
- Standard
- IEC 61482-1-2 (box test)
- Test
- 400 V, 500 ms, 4 kA (APC 1) or 7 kA (APC 2)
- Result
- Passed for class 1 or 2
Cal rating: ELIM, ATPV, EBT
Expressed in cal/cm².
- Standard
- IEC 61482-1-1 (open arc test)
- Test
- At what energy a second-degree burn can occur
- Result
- A number, for example ELIM 11.7 cal/cm²
Many garments have both: for example APC 1 with ELIM 11.7 cal/cm². A higher cal rating does not automatically mean a higher APC class.
Want to know more? Read our comprehensive article Arc flash clothing: APC 1, APC 2 and cal rating explained, with example sets per class, an explanation of the label and a checklist for employers.
How to choose the right protection
Determine the risk
The employer determines the required protection via the RI&E and an arc flash risk assessment according to NEN 3140 / NEN-EN 50110 (in Belgium the AREI).Choose a closed suit
Jacket and trousers, or an overall, of at least the required class or cal rating. Do not wear melting synthetic clothing underneath.Complete the set
Face shield or arc flash hood on the correct helmet, insulating gloves and, where necessary, insulating footwear.Compiled sets per class
| Set | Clothing | Face and head | Hands |
|---|---|---|---|
| APC 1 basic | Sioen Obera jacket with Sioen Zarate trousers, or Sioen Carlow overall (ELIM 11.7) | Petzl VERTEX with VIZEN | KCL Electro 583 (class 00) |
| APC 1 high-vis | Sioen Millau jacket with Sioen Royan trousers (ELIM 11.7) | Petzl VERTEX with VIZEN | KCL Electro 583 (class 00) |
| APC 1 Fristads | Fristads FLAM 4030 jacket with FLAM 0030 American overall (ELIM 8) | Petzl STRATO with VIZEN | KCL Electro 583 (class 00) |
| APC 2 | APC 2 jacket (Sioen Newton or Nash, HAVEP 50454) with trousers of at least APC 2 | Catu arc flash hood, MSA V-Gard 950 Class 2 or Kask ARC Visor Class 2 | KCL Electro 584 or Catu CGM-0 (class 0) |
Looking for an APC 2 trouser or overall? Ask us, and we will put together a suitable combination.
Equip a whole team?
Send us the number of employees, the sizes and the required class. You will receive a quote for the complete package, including gloves and face protection.
Request a team quote- One point of contact for clothing, PPE and documentation
- Documents from the manufacturer with every product
- Prices exclude VAT, business ordering
Questions about arc flash protection
What is the cal rating of arc flash clothing?
The cal rating (arc rating) indicates in cal/cm² how much heat energy from an arc flash the fabric withstands before a second-degree burn occurs. In Europe, ELIM is leading; ATPV and EBT are 50% values and are higher. Clothing that has only been tested in the box test has an APC class but no cal rating.
Is the cal rating on the garment itself?
The protection value is on the CE label on the inside of the garment, with the pictogram for arc flash protection. From the outside it is usually not visible. On the Catu arc flash hood, the label is on the outside. Per product, you can see under Specifications what exactly is on it.
What is the difference between flame retardant and arc flash resistant?
Flame retardant clothing (for example EN ISO 11612) extinguishes itself when the flame is gone. Arc flash resistant clothing (EN 61482-2) is additionally tested against the short, extreme heat of an arc flash. For electrical work with arc flash risk, you need the latter.
Is APC 2 always better than APC 1?
APC 2 is tested at a higher current (7 kA versus 4 kA) and thus offers more protection in the box test. Which class is needed depends on the installation and follows from the risk assessment. Heavier clothing is less comfortable, so choose what is needed.
Can I combine an APC 2 jacket with an APC 1 trouser?
Then you are protected according to APC 1 on the legs. The suit protects as well as the weakest part.
Can I layer, for example fleece under a jacket?
No. A combination only counts if the manufacturer has tested it as a whole. Do not wear synthetic clothing that can melt under arc flash clothing.
Can a company logo be on arc flash clothing?
Only according to the manufacturer's instructions, otherwise the certification may lapse. Fristads gives a maximum area for transfers and embroidery per model, and the Sioen Nash and Newton have a zipper in the lining for a logo. Ask us beforehand what is allowed per model.
How do I wash and maintain arc flash clothing?
Follow the wash label: no fabric softener, bleach or starch. Check the clothing before use for tears and contamination with oil or grease. After an arc flash incident, the garment must be replaced. Do not repair it yourself with regular fabric or thread.
What do NEN 3140 and the AREI mean for this?
NEN 3140 (Netherlands) and the AREI (Belgium) regulate how safely electrical installations are worked on. This results in the risk assessment with which the employer determines the required protection. In Belgium, this often concerns BA4 and BA5 authorized employees.
How often should insulating gloves be tested?
Check them before each use for damage (visually and with an air test) and have them periodically electrically tested according to EN 60903 and the manufacturer's instructions.
Need help with the right choice?
Let us know which installations your team works on and which class comes from the risk assessment. We will put together a suitable set.